PSR-SPP- 24UC/ESM4/3X1/1X2/B 数据手册
Extract from the online
catalog
PSR-SPP- 24UC/ESM4/3X1/1X2/B
Order No.: 2963925
The figure shows a version with a screw connection
http://catalog.phoenixcontact.net/phoenix/treeViewClick.do?UID=2963925
Safety relay to emergency stop and safety door monitoring up to SIL
3 or Cat. 4, PL e according to EN ISO 13849, one- or two-channel
operation, manual activation, 3 enabling current paths, nominal input
voltage 24 V AC/DC
Product notes
WEEE/RoHS-compliant since:
12/05/2006
Commercial data
EAN
4
017918
904760
sales group
G502
Pack
1 Pcs.
Customs tariff
85364900
Gross weight in pieces
0.2256 KG
Net weight per piece
0.19298 KG
Catalog page information
Page 21 (IF-2009)
http://
www.download.phoenixcontact.com
Please note that the data given
here has been taken from the
online catalog. For comprehensive
information and data, please refer
to the user documentation. The
General Terms and Conditions of
Use apply to Internet downloads.
Technical data
Input data
Nominal input voltage UN
24 V AC/DC
Input voltage range in reference to UN
0.85 ... 1.1
Typical input current at UN
140 mA AC
65 mA DC
Phoenix Contact (India) Pvt. Ltd.
http://www.phoenixcontact.co.in
Page 1 / 6
May 21, 2013
PSR-SPP- 24UC/ESM4/3X1/1X2/B Order No.: 2963925
http://catalog.phoenixcontact.net/phoenix/treeViewClick.do?UID=2963925
Voltage at input/start and feedback circuit
approx. 24 V DC
Typical response time
20 ms (Monitored/manual start)
Typical release time
45 ms (single-channel)
10 ms (two-channel)
Concurrence input 1/2
Infinite
Recovery time
1s
Max. permissible overall conductor resistance
approx. 50 Ω (Input and start circuits at UN)
Output data
Contact type
3 enabling current paths
1 signaling current path
Contact material
AgSnO2, + 0.2 µm Au
Maximum switching voltage
250 V AC/DC
Minimum switching voltage
15 V AC/DC
Limiting continuous current
6 A (N/O contact)
Maximum inrush current
6A
Inrush current, minimum
25 mA
Sq. Total current
72 A (ITH = I1 + I2 + I3 )
Interrupting rating (ohmic load) max.
144 W (24 V DC, τ = 0 ms)
2
2
2
2
2
288 W (48 V DC, τ = 0 ms)
77 W (110 V DC, τ = 0 ms)
88 W (220 V DC, τ = 0 ms)
1500 VA (250 V AC, τ = 0 ms)
Maximum interrupting rating (inductive load)
48 W (24 V DC, τ = 40 ms)
40 W (48 V DC, τ = 40 ms)
35 W (110 V DC, τ = 40 ms)
33 W (220 V DC, τ = 40 ms)
Switching capacity min.
0.4 W
Output fuse
10 A gL/gG NEOZED (N/O contact)
6 A gL/gG NEOZED (N/C contact)
General data
Width
22.5 mm
Height
112 mm
Depth
114.5 mm
Ambient temperature (operation)
-20 °C ... 55 °C
Phoenix Contact (India) Pvt. Ltd.
http://www.phoenixcontact.co.in
Page 2 / 6
May 21, 2013
PSR-SPP- 24UC/ESM4/3X1/1X2/B Order No.: 2963925
http://catalog.phoenixcontact.net/phoenix/treeViewClick.do?UID=2963925
Ambient temperature (storage/transport)
-40 °C ... 70 °C
Relay type
Electromechanically forcibly guided, dust-proof relay.
Mechanical service life
Approx. 10 cycles
Mounting position
Any
Category according to EN 13849-1
4
Stop category
0
Name
Air and creepage distances between the power circuits
Standards/regulations
DIN EN 50178/VDE 0160
Rated surge voltage / insulation
4 kV / Basic isolation, (safe isolation, reinforced insulation and 6
kV between input circuit and enabling current paths.)
Rated insulation voltage
250 V
Pollution degree
2
Surge voltage category
III
7
Connection data
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
1.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
1.5 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
16
Stripping length
8 mm
Connection method
Spring-cage conn.
Certificates / Approvals
Certification
cULus Listed, GOST, Functional Safety
Certifications applied for:
Certification Ex:
Phoenix Contact (India) Pvt. Ltd.
http://www.phoenixcontact.co.in
Page 3 / 6
May 21, 2013
PSR-SPP- 24UC/ESM4/3X1/1X2/B Order No.: 2963925
http://catalog.phoenixcontact.net/phoenix/treeViewClick.do?UID=2963925
Drawings
Application drawing
Example of a safety door application with a PSR safety relay
PSR-ESM4.
Circuit diagram
1 = logics
a = RESET
b = Emergency stop
One-channel emergency stop circuit with
manual activation, suitable up to safety
category 2
Phoenix Contact (India) Pvt. Ltd.
http://www.phoenixcontact.co.in
Page 4 / 6
May 21, 2013
PSR-SPP- 24UC/ESM4/3X1/1X2/B Order No.: 2963925
http://catalog.phoenixcontact.net/phoenix/treeViewClick.do?UID=2963925
a = RESET
b = Emergency stop
Two-channel emergency-stop circuit with
manual activation and monitored contact
expansion (automatic activation: Bridge on
S33/S35), suitable up to safety category 3.
Phoenix Contact (India) Pvt. Ltd.
http://www.phoenixcontact.co.in
Page 5 / 6
May 21, 2013
PSR-SPP- 24UC/ESM4/3X1/1X2/B Order No.: 2963925
http://catalog.phoenixcontact.net/phoenix/treeViewClick.do?UID=2963925
Address
Phoenix Contact (India) Pvt. Ltd.
A-58/2, Okhla Industrial Area, Phase - II,
IND-New Delhi-110 020,India
Phone +91.11.30 262 800/700
Fax +91.11.26 383 285, 41611-070/71
http://www.phoenixcontact.co.in
© 2012 Phoenix Contact
Technical modifications reserved;
Phoenix Contact (India) Pvt. Ltd.
http://www.phoenixcontact.co.in
Page 6 / 6
May 21, 2013
PSR-SPP- 24UC/ESM4/3X1/1X2/B 价格&库存
很抱歉,暂时无法提供与“PSR-SPP- 24UC/ESM4/3X1/1X2/B”相匹配的价格&库存,您可以联系我们找货
免费人工找货